Horizontal or Vertical Wall Panels.
Versatile, maintenance-free, prefinished metal wall panels
for open spans
Berridge's new HR-16 wall panels is a 16"
coverage panel designed for horizontal applications. HR-16
has 4 ribs spaced 4 inches on center and is 7/8" deep.
- Hidden Fasteners
- Extruded Rib Appearance
- Multi-Purpose Panel
- Available in 24 or 22 ga.
PDF Catalog Sheet
Installation Details
Specifications
File (MS Word Doc)
HR-16 SPECIFICATIONS
To use
these specs in your project document, just use your mouse to drag and select all
specification copy, then copy to the clipboard (CTRL - C), then paste into an
open document (CTRL -V).
MANUFACTURER
Berridge Manufacturing
Company
6515 Fratt Road
San Antonio, TX 78218
Phone: (800) 669-0009 Outside TX
(210) 650-3050 In TX
Fax: (210) 650-0379
SECTION
07 41 00
PREFORMED
METAL WALL PANELS
PART 1 GENERAL
1.01 SECTION INCLUDES
A. Preformed, prefinished
metal wall panels and flashings.
B. Miscellaneous trim,
flashing, closures and accessories.
C. Fastening devices.
1.02 RELATED SECTIONS
A. Section 05120:
Structural Steel Framing.
B. Section 05500:
Miscellaneous metal fabrication.
C. Section 06100: Rough
Carpentry.
D. Section 07631: Flashing.
1.03 REFERENCES
A. American Iron & Steel
Institute (AISI) Specification for the Design of Coldformed
Steel Structural Members.
B. ASTM A-525 Steel Sheet,
Zinc-Coated (Galvanized)
C. SMACNA - Architectural
Sheet Metal Manual.
1.04 ASSEMBLY
DESCRIPTION
A. The wall assembly
includes preformed sheet metal panels, related accessories,
miscellaneous flashing and attaching devices.
1.05 SUBMITTALS
A. Submit detailed drawings
showing layout of panels, anchoring details, joint details,
trim, flashing, and accessories. Show details of
weatherproofing, terminations, and penetrations of metal
work.
B. Submit a sample of
each type of wall panel, complete with factory finish.
1.06 QUALITY ASSURANCE
A. Manufacturer: Company
specializing in Architectural Sheet Metal Products with ten
(10) years minimum experience.
B. No product substitutions
shall be permitted without meeting specifications.
C. Substitutions shall be
submitted 10 Days prior to Bid Date and acceptance put
forth in an addendum.
D. No substitutions shall
be made after the Bid Date.
1.07 DELIVERY, STORAGE
AND HANDLING
A. Upon receipt of panels
and other materials, installer shall examine the shipment
for damage and completeness.
B. Panels should be stored
in a clean, dry place. One end should be elevated to allow
moisture to run off.
C. Panels with strippable
film must not be stored in the open, exposed to the sun.
D. Stack all materials to
prevent damage and to allow for adequate ventilation.
1.08 WARRANTY
A. Paint finish shall have
a twenty year warranty against cracking, peeling and fade
(not to exceed 5 N.B.S. units).
B. Galvalume material shall
have a twenty year warranty against failure due to
corrosion, rupture or perforation.
C. Applicator shall furnish
warranty covering watertightness of the wall system for the
period of two (2) years from the date of substantial
completion.
PART 2 PRODUCT
2.01 ACCEPTABLE
MANUFACTURERS
A. Berridge Manufacturing
Company, Houston, Texas.
B. Substitutions shall
fully comply with specified requirements.
2.02 SHEET MATERIALS
A. Prefinished Metal shall
be [Hot-Dipped Galvanized - ASTM A653-94 Grade C G90 Coating
A924-94 24 Gauge core steel] or [prefinished Galvalume 24
Gauge core steel - ASTM 792-86 AZ-55 ].
B. Unfinished Metal shall
be Grade C Aluminum Zinc Alloy Coated Steel ASTM 792-86, AZ
55, "Satin Finish".
C. Finish shall be full
strength Kynar 500 PVDF resin-based coating, applied by the
manufacturer on a continuous coil coating line, with a top
side dry film thickness of 0.70 to 0.80 mil over 0.20 to
0.30 mil prime coat, to provide a total topside dry film
thickness of 1.0 plus or minus 0.10 mil. Reverse side shall
be coated with primer and wash coat of 0.30 mil plus or
minus 0.05 mil. Finish shall conform to all tests for
adhesion, flexibility, and longevity as specified by the
Kynar 500 PVDF resin-based coating supplier.
D. Strippable film shall be
applied to the top side of the painted coil to protect the
finish during fabrication, shipping and field handling.
This strippable film must be removed immediately before
installation.
2.03 ACCESSORY MATERIALS
A. Concealed fasteners:
Galvanized Steel.
2.04 FABRICATION
A. All exposed adjacent
flashing shall be of the same material and finish as the
roof panels.
B. Hem all exposed edges of
flashing on underside, 1/2 inch.
2.05 PREFORMED WALL
PANELS
BERRIDGE HR-16 WALL PANEL
1. Panel coverage width to
be 16", with a panel depth of 7/8".
2. Ribs to be spaced 4" on
center.
3. Panels to be of
interlocking design with concealed fasteners.
PART 3 EXECUTION
3.01 INSPECTION
A. Substrate:
1. Minimum 1/2" plywood,
24-gauge metal deck or open framed purlins at 4' o.c.
2. Inspect framing to
verify free of depressions, waves or projections,
level to ¼" in 20'
3. Verify openings,
curbs, pipes, sleeves, ducts or vents through wall are
solidly set.
B. Underlayment:
1. Verify one layer of #30
unperforated asphalt saturated roofing felt
underlayment has been installed over solid plywood or
taped polyurethane sheet over open framing.
2. Ensure felt installed
horizontally, starting top, with a 6" minimum overlap and
18" endlaps.
5. Ensure that all nail
heads are totally flush with the substrate. Nails shall be
galvanized roofing nails with Berridge Coated Felt Caps.
3.02 INSTALLATION
A. Comply with
manufacturers standard instructions and conform to standards
set forth in the Architectural Sheet Metal Manual published
by SMACNA, in order to achieve a watertight installation.
B. Install panels in such a
manner that horizontal lines are true and level and vertical
lines are plumb.
D. Remove protective
strippable film prior to installation of panels.
E. Attach panels using
manufacturer’s standard clips and fasteners, spaced in
accordance with approved shop drawings.
F. Do not allow panels or
trim to come into contact with dissimilar materials.
G. Remove and replace any
panels or components which are damaged beyond successful
repair.
3.03 CLEANING
A. Clean any grease, finger
marks or stains from the panels per manufacturer’s
recommendations.
B. Remove all scrap and
construction debris from the site.
3.04 FINAL INSPECTION
A. Final inspection will be
performed by a firm appointed and paid for by the owner in
accordance with section 01410.
END OF SECTION
NOTE:
Please reference Berridge Manufacturing Company’s current
Sweet’s Catalog 07 61 00/BER , Sweet's BuyLine 49510 and 07
41 00/BER and Berridge's website at www.berridge.com for
standard product offering with regard to materials, gauges,
finishes and colors available.